How Often Do Fire Extinguishers Need Servicing?

Updated 13 October 2026 · Abbey Fire Safety

Short answer

Every 12 months by a competent engineer, plus a quick visual check by you or your staff at least once a month. Most extinguishers also need an extended service, with a test discharge, every 5 years, and CO2 extinguishers need an overhaul or replacing at 10 years.

The law and the standard

The Regulatory Reform (Fire Safety) Order 2005 says firefighting equipment must be kept in efficient working order and good repair. The detail comes from BS 5306-3, the British Standard for extinguisher maintenance, which is what fire officers and insurers expect you to follow.

The annual service

Once a year a competent engineer should:

  • check each extinguisher still suits the hazard it covers
  • check the safety pin and tamper seal
  • inspect the body, head cap and hose
  • check the pressure gauge
  • weigh it to check the charge
  • replace worn O-rings
  • check the wall bracket and sign
  • fit a new service label
  • give you a written report

If an extinguisher fails, it gets a corrective action label and the report says what needs doing.

The 5 and 10 year extended service

Water, foam, wet chemical and powder extinguishers need an extended service every 5 years, where they are test-discharged and refilled or replaced. CO2 extinguishers do not have a 5-year discharge; instead they need an overhaul, including a pressure test, at 10 years. Most businesses find replacing a 10-year-old CO2 is better value.

Your monthly check

At least once a month, check each extinguisher is:

  • in its proper place
  • not blocked and easy to see
  • showing clean, readable instructions facing outwards
  • not used, damaged or missing parts
  • showing a pressure gauge in the green
  • still sealed with its tamper tag

Write the check in your fire safety logbook.

What the service label tells you

The label usually shows the date of the service, the engineer and when the next service is due. If the last service date is more than a year ago, it is time to book a service.

Frequently Asked Questions

Can't find what you're looking for? We're happy to help.

How often do fire extinguishers need servicing?
Every 12 months by a competent person under BS 5306-3, plus a monthly visual check by you or your staff.
What is an extended service?
Every 5 years, water, foam, wet chemical and powder extinguishers are test-discharged and refilled or replaced. CO2 extinguishers need an overhaul or replacement at 10 years instead.
Can I service my own extinguishers?
You can and should do the monthly visual check yourself. The annual service should be done by a competent engineer, who leaves a written record for your files.

Need a hand with fire safety?

Get expert fire safety support with over 30 years of experience across Dorset, Wiltshire, Hampshire and beyond. You'll receive a free site survey and only ever be recommended what you genuinely need. No overselling, no unnecessary costs.