Emergency Lighting Testing: What You Need to Do

Updated 13 October 2026 · Abbey Fire Safety

Short answer

Test every emergency light with a short flick test once a month, and have a competent engineer carry out a full-duration test, usually 3 hours, once a year. Record both in your logbook. BS 5266-1:2025 also asks for light levels to be checked at least every 5 years.

The law and the standards

The Fire Safety Order requires escape routes that need lighting to have emergency lighting that works if the mains fails. BS 5266-1 is the code of practice. The 2025 edition came into effect on 31 October 2025, alongside BS EN 50172:2024.

The monthly flick test

Once a month, simulate a mains failure using the test key switch (not the main power switch) and check every emergency light and lit exit sign comes on. Then restore the power and check the charging lights are back on. You or trained staff can do this.

The annual full-duration test

Once a year, each light must run on battery for its full rated time, usually 3 hours. This should be done by a competent person, who gives you a certificate. Batteries can take up to 24 hours to recharge afterwards, so plan it for a quiet time.

Records

Keep a record of every monthly and annual test in the logbook, with the date, results, faults and what was done about them. Fire officers will ask to see it.

What changed in 2025

The 2025 edition covers standby and local area lighting as well as escape lighting, asks for light levels to be checked at intervals of no more than 5 years, and sets clearer minimum light levels, including at least 1 lux across escape route floors and 5 lux at extinguishers, call points and first aid points.

Frequently Asked Questions

Can't find what you're looking for? We're happy to help.

How often should emergency lighting be tested?
A short flick test every month and a full-duration test, usually 3 hours, once a year, with both written in the logbook.
Can I test my own emergency lights?
Yes, you or trained staff can do the monthly flick test. The annual full-duration test and certificate should be done by a competent engineer.
What changed in BS 5266-1:2025?
It now covers standby and local area lighting, asks for light levels to be checked at least every 5 years, and sets clearer minimum light levels for escape routes and safety equipment.